Detail:
A PANEL DESIGNED FOR CONNECTING, DISCONNECTING AND PROTECTING POWER LINE FEEDERS AND/OR DIRECT CONTROL OF SPECIFIC ELECTRIC DEVICES SUCH AS LIGHTS, MOTORS, ELECTRONIC EQUIPMENT, ETC. SEE ALSO FUSE BOX; SWITCH BOX; DISTRIBUTION BOX; AND PANEL, POWER BUS, CIRCUIT BREAKER.


Manufacturer Information:
600260880091NAVAL FACILITIES ENGINEERING COMMAND


Techincal Specification:
ELECTRICAL INPUT QUANTITY1
ELECTRICAL OUTPUT QUANTITY7
ENCLOSURE FEATUREWATERPROOF
INPUT FREQUENCY IN HERTZ60.0
INPUT VOLTAGE RATING480.0 AC VOLTS MAXIMUM
INPUT PHASETHREE
OUTPUT FREQUENCY RATING60 HERTZ
OUTPUT VOLTAGE RATING120.0 AC VOLTS MINIMUM AND 208.0 AC VOLTS MAXIMUM
OVERALL HEIGHT40.000 INCHES MAXIMUM
OVERALL LENGTH72.000 INCHES MAXIMUM
OVERALL WIDTH36.000 INCHES MAXIMUM
PANEL MATERIALALUMINUM
PANEL QUANTITY1
MOUNTING METHODFLOOR
NONDEFINITIVE SPEC/STD DATAII TYPE AND 2 CLASS
PHASETHREE
SPECIAL FEATURESPORTABLE ASSEMBLED UNIT ARRANGED SO IT CAN BE LIFTED BY A FORK LIFT,PROVIDED W/TOW BAR AND SLED,CONSISTS OF2 3-POLE CIRCUIT BREAKERS,225 AMP,480V,3 3-POLE CIRCUIT BREAKERS,100 AMP,480V,1 3-POLE CIRCUIT BREAKER,70AMP,480V,4 3-POLE CIRCUIT BREAKERS,30 AMP,208V,2 2-POLE CIRCUIT BREAKERS,50 AMP,208V,1 3-POLE CIRCUIT BREAKER,100 AMP,208V,8 GROUND FAULT CIRCUIT BREAKERS,20 AMP,120V CONNECTED TO NEMA RECEPTACLES,3 10KVA,480-120V 10 TRANSFORMERS CONNECTED 480-208V/120 FOR 30KVA CAPACITY,1 GROUND LUG CONNECTOR