5905-00-211-0203 RESISTOR,VARIABLE,NONWIRE WOUND, Index 5905-00-211-0206 RESISTOR,FIXED,FILM

National Stock Number:
5925-00-211-0205

Federal Supply Class:
5925

National Item Identification Number:
002110205

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
JA3-A2A3A3-A-10-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
JA3A2A3A10-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
JA3S-A2A3A3-A-10-274193EATON CORP HEINEMANN PRODUCTS COMMERCIAL CONTROLS DIV
UPG-111-1REC2-62-103-0981541SENSATA TECHNOLOGIES MARYLAND, INC


Techincal Specification:
BODY STYLEMULTIPOLE-MULTIPLE ACTUATOR TYPE
MOUNTING FACILITY TYPE AND QUANTITY6 THREADED HOLE
CASE MATERIALPLASTIC
UNPACKAGED UNIT WEIGHT0.440 POUNDS NOMINAL
TRIP RELEASE METHODMAGNETIC-HYDRAULIC ALL LOCATIONS
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS1000.0 AC ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSERIES TRIP ALL LOCATIONS
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT2.200 MINIMUM AT 200 PCT AND
20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT125.0 ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
BODY LENGTH1.985 INCHES MINIMUM AND
2.015 INCHES MAXIMUM
BODY WIDTH2.245 INCHES MINIMUM AND
2.255 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.555 INCHES MINIMUM AND
1.565 INCHES MAXIMUM
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH0.745 INCHES MINIMUM AND
0.755 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH1.655 INCHES MINIMUM AND
1.665 INCHES MAXIMUM
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH0.745 INCHES MINIMUM AND
0.755 INCHES MAXIMUM
BOSS HEIGHT0.125 INCHES MINIMUM AND
0.135 INCHES MAXIMUM
MOUNTING SURFACE TO TERMINAL END DISTANCE1.835 INCHES MINIMUM AND
1.845 INCHES MAXIMUM
THREAD SERIES DESIGNATORUNC
NOMINAL THREAD SIZE0.138 INCHES
THREAD QUANTITY PER INCH32
MANUAL ACTUATOR TYPE AND QUANTITY3 TOGGLE
ACTUATOR FUNCTIONTRIP-RESET
ACTUATOR POSITION DESIGNATIONAT EACH POLE
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
AUXILIARY SWITCH FUNCTION AND QUANTITY1 ALARM
SWITCH LOCATION AND POSITION DESIGNATIONINTERNAL AT POLE THREE
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS10.0 AC AND
4.0 DC
SWITCH VOLTAGE RATING AND TYPE IN VOLTS250.0 AC AND
30.0 DC
SWITCH TERMINAL TYPEQUICK DISCONNECT, MALE
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNEDFUNGUS RESISTANT AND
MOISTURE RESISTANT
ARC QUENCHING METHODMAGNETIC BLOWOUT
STORAGE TYPEGENERAL PURPOSE WAREHOUSE
SPECIAL HANDLING FEATUREMAGNETIC
FRAGILITY FACTORMODERATELY RUGGED
POLE QUANTITY3
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE10.0 AMPERES AC ALL LOCATIONS
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
TERMINAL TYPE AND QUANTITY6 TAB, SOLDER LUG
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS250.0 AC ALL LOCATIONS
TRIP RELEASE CHARACTERISTICTIME DELAY ALL LOCATIONS
RESET METHODMANUAL


Click here to Register for Free 30-day Trial