5950-00-196-3996 COIL,RADIO FREQUENCY Index 1730-00-196-4009 REPAIR KIT,UNIVERSAL TOWBAR

National Stock Number:
5925-00-196-3997

Federal Supply Class:
5925

National Item Identification Number:
001963997

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
150-086652151CONTINENTAL ELECTRONICS CORP


Techincal Specification:
ACTUATOR FUNCTIONRESET
ACTUATOR POSITION DESIGNATIONAT POLE ONE
ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS+280.0 TO 460.0 AC AND +1750.0 TO 5250.0 AC ALL LOCATIONS
AUXILIARY SWITCH FUNCTION AND QUANTITY12 ALARM
BODY HEIGHT17.000 INCHES NOMINAL
BODY LENGTH17.562 INCHES NOMINAL
BODY STYLEMULTIPOLE-SINGLE ACTUATOR TYPE
BODY WIDTH12.750 INCHES NOMINAL
BOSS HEIGHT0.375 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH1.375 INCHES NOMINAL
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH3.625 INCHES NOMINAL
CIRCUIT PROTECTION TYPEOVERCURRENT ALL LOCATIONS
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH11.625 INCHES NOMINAL
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH10.562 INCHES NOMINAL
EXTERNAL ACTUATOR LINKAGE ARRANGEMENTONE, TWO, AND THREE LINKED
FEATURES PROVIDEDADJUSTABLE TRIP RELEASE
FREQUENCY IN HERTZ60.0 ALL LOCATIONS
INTERNAL TRIP RELEASE CONFIGURATIONSHUNT TRIP ALL LOCATIONS
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
MANUAL ACTUATOR TYPE AND QUANTITY1 ROTARY
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE600.0 AMPERES AC ALL LOCATIONS
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS3500.0 AC ALL LOCATIONS
MOUNTING FACILITY TYPE AND QUANTITY4 SLOT AND 4 UNTHREADED HOLE
MOUNTING SLOT WIDTH0.187 INCHES NOMINAL
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS600.0 AC ALL LOCATIONS
POLE QUANTITY3
RESET ACTUATOR VOLTAGE RATING AND TYPE IN VOLTS208.0 AC
RESET METHODELECTRIC
SPECIAL FEATURESLONG DELAY PICKUP,LONG TIME DELAYBAND,INSTANTANEOUS PICKUP SETTINGS ADJUSTABLE.
SWITCH CONTACT ARRANGEMENTSINGLE POLE, DOUBLE THROW
SWITCH CURRENT RATING AND TYPE IN AMPS12.0 AC AND 9.0 DC
SWITCH TERMINAL TYPETHREADED STUD
SWITCH VOLTAGE RATING AND TYPE IN VOLTS208.0 AC AND 120.0 DC
TERMINAL TYPE AND QUANTITY6 BUS BAR
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT75.000 MINIMUM AT 100 PCT AND 1000.000 MAXIMUM AT 100 PCT AND 56.000 MINIMUM AT 150 PCT AND 200.000 MAXIMUM AT 150 PCT AND 46.000 MINIMUM AT 200 PCT AND 300.000 MAXIMUM AT 200 PCT AND 40.000 MINIMUM AT 300 PCT AND 150.000 MAXIMUM AT 300 PCT AND 34.000 MINIMUM AT 400 PCT AND 90.000 MAXIMUM AT 400 PCT AND 28.000 MINIMUM AT 500 PCT AND 65.000 MAXIMUM AT 500 PCT AND 10.000 MINIMUM AT 1000 PCT AND 18.000 MAXIMUM AT 1000 PCT ALL LOCATIONS
TRIP RELEASE CHARACTERISTICINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
TRIP RELEASE METHODMAGNETIC ALL LOCATIONS
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT150.0 ALL LOCATIONS
ULTIMATE TRIP TIME PER POLE IN SECONDS56.000 NOMINAL ALL LOCATIONS
UNTHREADED MOUNTING HOLE DIAMETER0.500 INCHES NOMINAL