5925-00-175-2593 CIRCUIT BREAKER Index 5925-00-175-2597 CIRCUIT BREAKER

National Stock Number:
5925-00-175-2595

Federal Supply Class:
5925

National Item Identification Number:
001752595

Description:
CIRCUIT BREAKER

Detail:
A DEVICE WITH MEANS OTHER THAN FUSES FOR AUTOMATICALLY OPENING THE CIRCUIT IN WHICH IT IS INSTALLED WHEN THE CURRENT VARIES FROM THE PREDETERMINED VALUE FOR WHICH THE DEVICE IS SET. MAY INCLUDE PROVISIONS FOR MANUAL OPERATION. AT LEAST ONE SET OF CONTACTS MUST BE IN SERIES WITH THE ACTUATING ELEMENT(S). A COMBINATION OF SEMICONDUCTOR AND PASSIVE DEVICES MAY BE USED IN LIEU OF CONTACTS. FOR AUTOMATICALLY OPERATED ITEMS IN WHICH THE ACTUATING (TRIPPING) ELEMENT AND CONTACTS ARE NOT IN SERIES, SEE RELAY (AS MODIFIED). FOR ITEMS WHICH ARE OPERATED BOTH MANUALLY AND AUTOMATICALLY BUT THE ACTUATING ELEMENTS AND CONTACT ARE NOT IN SERIES, SEE RELAY-SWITCH. EXCLUDES CIRCUIT BREAKER BOX AND MAGNETO "BREAKER" ASSEMBLIES. SEE ALSO SWITCH (AS MODIFIED); AND CONTROLLER.


Manufacturer Information:
CA1582647SENSATA TECHNOLOGIES, INC.


Techincal Specification:
CIRCUIT PROTECTION TYPEOVERCURRENT SINGLE LOCATION
MAIN CONTACT TRIPPING MECHANISM TYPETRIP FREE
OVERALL HEIGHT1.281 INCHES NOMINAL
OVERALL LENGTH2.000 INCHES NOMINAL
OVERALL WIDTH1.188 INCHES NOMINAL
MATERIALPLASTIC CASE
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE15.0 AMPERES AC AND 15.0 AMPERES DC SINGLE LOCATION
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS300.0 AC AND 300.0 DC SINGLE LOCATION
MOUNTING FACILITY TYPE AND QUANTITY2 UNTHREADED HOLE
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS30.0 AC AND 30.0 DC SINGLE LOCATION
POLE QUANTITY1
RESET METHODAUTOMATIC
TERMINAL TYPE AND QUANTITY2 SCREW
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT200.000 NOMINAL AT 125 PCT AND 6.500 NOMINAL AT 200 PCT AND 1.600 NOMINAL AT 300 PCT SINGLE LOCATION
TRIP RELEASE AMBIENT TEMP RATING25.0 CELSIUS NOMINAL SINGLE LOCATION
TRIP RELEASE CHARACTERISTICTIME DELAY SINGLE LOCATION
TRIP RELEASE METHODTHERMAL SINGLE LOCATION
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT113.0 SINGLE LOCATION
UNTHREADED MOUNTING HOLE DIAMETER0.188 INCHES NOMINAL


Click here to Register for Free 30-day Trial