ADJUSTABLE TRIP SETTING CURRENT RANGE PER POLE IN AMPS | +960.0 TO 1600.0 AC ALL LOCATIONS |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 CONTROL |
BODY STYLE | RECTANGULAR DIMENSIONAL ENVELOPE |
CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
FREQUENCY IN HERTZ | 60.0 ALL LOCATIONS |
MANUAL ACTUATOR TYPE AND QUANTITY | 1 ROTARY |
OVERALL HEIGHT | 13.000 INCHES NOMINAL |
OVERALL LENGTH | 24.000 INCHES NOMINAL |
OVERALL WIDTH | 13.000 INCHES NOMINAL |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 640.0 AMPERES AC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 40000.0 AC ALL LOCATIONS |
MOUNTING FACILITY TYPE AND QUANTITY | 6 UNTHREADED HOLE |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 500.0 AC ALL LOCATIONS |
POLE QUANTITY | 3 |
REFERENCE NUMBER DIFFERENTIATING CHARACTERISTICS | AS DIFFERENTIATED BY POLE QUANTITY,MAXIMUM CONTINUOUS LOAD CURRENTPER POLE,OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS |
RESET METHOD | AUTOMATIC |
TERMINAL TYPE AND QUANTITY | 6 BUS BAR |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 20.000 NOMINAL AT 200 PCT ALL LOCATIONS |
TRIP RELEASE CHARACTERISTIC | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 150.0 ALL LOCATIONS |
UNTHREADED MOUNTING HOLE DIAMETER | 0.562 INCHES NOMINAL |