POLE QUANTITY | 2 |
MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 50.0 AMPERES DC ALL LOCATIONS |
CIRCUIT PROTECTION TYPE | OVERCURRENT FIRST LOCATION |
| OVERVOLTAGE SECOND LOCATION |
TERMINAL TYPE AND QUANTITY | 6 THREADED STUD |
OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 125.0 DC FIRST LOCATION |
| 30.0 DC SECOND LOCATION |
TRIP RELEASE CHARACTERISTIC | TIME DELAY FIRST LOCATION |
| INSTANTANEOUS SECOND LOCATION |
RESET METHOD | MANUAL |
BODY STYLE | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
MOUNTING FACILITY TYPE AND QUANTITY | 4 THREADED HOLE AND |
| 4 SLOT |
CASE MATERIAL | PLASTIC |
UNPACKAGED UNIT WEIGHT | 1.300 POUNDS NOMINAL |
TRIP RELEASE METHOD | MAGNETIC ALL LOCATIONS |
MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 DC ALL LOCATIONS |
INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP FIRST LOCATION |
| RELAY TRIP SECOND LOCATION |
TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 30.000 MINIMUM AT 200 PCT AND |
| 100.000 MAXIMUM AT 200 PCT FIRST LOCATION |
ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 FIRST LOCATION |
MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
BODY LENGTH | 4.750 INCHES NOMINAL |
BODY WIDTH | 2.072 INCHES MAXIMUM |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO LENGTH | 3.547 INCHES NOMINAL |
CENTER TO CENTER DISTANCE BETWEEN TERMINALS PARALLEL TO WIDTH | 1.026 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY LENGTH | 2.750 INCHES NOMINAL |
DISTANCE BETWEEN CENTERLINES OF MOUNTING FACILITIES PARALLEL TO BODY WIDTH | 1.026 INCHES NOMINAL |
BOSS HEIGHT | 0.219 INCHES NOMINAL |
MOUNTING SURFACE TO TERMINAL END DISTANCE | 3.485 INCHES NOMINAL |
THREAD SERIES DESIGNATOR | UNC |
NOMINAL THREAD SIZE | 0.138 INCHES |
THREAD QUANTITY PER INCH | 32 |
MOUNTING SLOT WIDTH | 0.164 INCHES NOMINAL |
MANUAL ACTUATOR TYPE AND QUANTITY | 2 TOGGLE |
ACTUATOR FUNCTION | TRIP-RESET |
ACTUATOR POSITION DESIGNATION | AT EACH POLE |
EXTERNAL ACTUATOR LINKAGE ARRANGEMENT | ONE AND TWO LINKED |
AUXILIARY SWITCH FUNCTION AND QUANTITY | 1 ALARM |
SWITCH LOCATION AND POSITION DESIGNATION | INTERNAL AT POLE ONE |
SWITCH CONTACT ARRANGEMENT | SINGLE POLE, DOUBLE THROW |
SWITCH CURRENT RATING AND TYPE IN AMPS | 5.0 AC |
SWITCH VOLTAGE RATING AND TYPE IN VOLTS | 125.0 AC |
SWITCH TERMINAL TYPE | TAB, SOLDER LUG |
INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | VIBRATION RESISTANT AND |
| SHOCK RESISTANT AND |
| MOISTURE RESISTANT AND |
| SALT SPRAY PROOF AND |
| FUNGUS RESISTANT |
TEST DATA DOCUMENT | 80063-SM-A-742924 DRAWING (THIS IS THE BASIC GOVERNING DRAWING, SUCH AS A CONTRACTOR DRAWING, ORIGINAL EQUIPMENT MANUFACTURER DRAWING, ETC.; EXCLUDES ANY SPECIFICATION, STANDARD OR OTHER DOCUMENT THAT MAY BE REFERENCED IN A BASIC GOVERNING DRAWING) |
STORAGE TYPE | GENERAL PURPOSE WAREHOUSE |
SPECIAL HANDLING FEATURE | MAGNETIC |
FRAGILITY FACTOR | MODERATELY RUGGED |